Fire alarm wiring is a craft learned not just from codes and cut sheets, but from basements at 2 a.m., after-hours suite buildouts, and dusty riser rooms where the as-builts don’t match reality. Class A and Class B circuits for smoke and heat detector wiring look simple on paper. In practice, the topology you choose ripples through survivability, cost, troubleshooting, and how your emergency evacuation system wiring performs when the building is under stress. This is a field where trade-offs matter and where “good enough” can turn into a false alarm count that your client never forgets.
What Class A and Class B actually mean
Both Class A and Class B refer to how initiating device circuits (IDCs) and signaling line circuits (SLCs) are wired to maintain continuity under fault conditions. The National Fire Alarm and Signaling Code, commonly NFPA 72, defines performance requirements rather than mandating one topology. Manufacturers layer their own rules on top, especially for addressable systems. The concepts:
Class B is a single run from the control unit out to the last device, with an end-of-line (EOL) device used for supervision. A single open anywhere past the panel breaks communication with everything beyond the fault. A short typically drops the entire loop, depending on device isolation and panel design.
Class A forms a loop that leaves the panel, passes through devices, and returns to the panel on a separate path. With proper isolation and programming, a single open does not interrupt communication to any device, and the panel identifies the fault while maintaining operation. Shorts get localized by isolators so the rest of the loop functions.
That’s the broad picture. The details get more nuanced once you consider addressable SLCs, conventional IDCs, NAC circuits, and power-limited requirements.
Where each class fits in real buildings
Class B has earned its place by being straightforward and economical. For many light commercial occupancies and small multi-tenant buildings, a well-installed Class B layout is reliable, easy to troubleshoot, and code-compliant. If you’re wiring an office buildout with a dozen addressable detectors and a few modules for elevator recall and duct detection, Class B might be the right call if the risk analysis says the downtime from a single open is acceptable.
Class A comes into the conversation when the building or the owner expects higher survivability. Hospitals, high-rise core and shell, arenas, data centers, and facilities where egress depends on coordinated control are common candidates. If a single cable break could isolate twenty floors of devices, Class A starts to look cheap compared to the risk. A life safety wiring design that loops back to the panel gives a second path, which can be critical during demolition phases, tenant turnover, or ongoing construction where cable damage is likely.
I once walked a university science building after a subcontractor drilled a raceway path through a chase. A single Class B open, caused by the bit catching the cable, knocked out an entire wing. They were lucky it happened at 10 a.m. during testing. The upgrade to Class A on the renovated floors paid for itself in one semester thanks to reduced service calls and fewer disruptions.
Addressable SLCs, isolation, and practical survivability
Many addressable control panels market Class A capability, but the survivability you get depends heavily on isolator placement and routing. Isolator modules or built-in isolators in devices segment the loop so a short gets trapped, allowing the rest of the SLC to function. Without enough isolators, a short can still cripple half the loop.
A solid rule of thumb is to isolate vertical transitions, long corridor runs, and anywhere routes converge. Spread the isolators so they bracket larger risk sections rather than clustering them near the panel. In hospitals, I isolate per smoke compartment. In high-rise towers, I drop isolators per floor and sometimes per riser leg, so a single fault cannot blind a stairwell or an elevator lobby sequence.

The panel’s annunciator panel setup matters too. Good mapping between SLC addresses and the building plan lets the operator see not just a trouble, but where the cable fault sits, which riser it rides, and which zones are still fully functional. That translates directly into faster repair and less confusion during a live event.
Conventional inputs, EOL discipline, and the myth of “any end will do”
With conventional Class B IDCs, the EOL resistor belongs at the last device. Any shortcut, such as putting the resistor in the panel or in a junction box near the panel, defeats supervision of the field wiring. I have chased intermittent troubles for hours only to discover the EOL stuffed inside the panel during construction to “get it to pass” while waiting on ceiling tiles. That practice becomes permanent too often, and it removes the very protection that Class B depends on.
Class A conventional circuits are less common on new work, since addressable systems have taken over, but they remain in the field. When you do convert an old Class B conventional IDC to Class A, verify the panel supports that mode on the selected circuits, and survey the existing cable for enough conductors. The extra pair for the return path is not optional. Avoid the temptation to share conductors with NACs or auxiliary power. Separation meets code for good reasons, including noise immunity and fault containment.
NACs and notification strategy under fault
Notification appliance circuits (NACs) are legally and ethically different from initiating circuits. If a NAC fails, occupants may miss life-saving audible or visual cues. NACs can be Class A or Class B too, and in some hospitals and high-rise facilities I design per-floor NAC Class A routing so a single open does not silence a whole floor. Strobes with synchronized patterns load the circuit in distinct ways, and long runs create voltage drop issues. All of that compounds when you try to route Class A through large buildings.
A reliable approach pairs Class A for critical floors and Class B elsewhere, with careful distribution of NAC power supplies. If you need mass notification cabling for voice evacuation, prioritize survivability in the backbone paths feeding amplifiers and risers. For voice, speaker circuit zoning that mirrors smoke compartments and stairwells is far more important than any label on the topology. A well-zoned Class B voice circuit with local amplifiers in separate fire-rated enclosures can outperform a poorly routed Class A that shares too many common pathways.
Cable types, pathways, and the physics behind nuisance faults
Most fire alarm installation drawings call for power-limited fire alarm cable, plenum or riser rated per space type. That’s table-stakes. Where projects fail is in pathway strategy. I avoid having the outbound and return legs of a Class A loop run in the same conduit for any significant distance. A single conduit hit takes out both legs. Codes allow it in some cases, but from a survivability perspective it defeats the point. Where architecture allows, route the return path using a different riser or a different side of the corridor. Use red conduit or labels to help other trades respect the separation.
Noise immunity plays a role too. Addressable SLCs are resilient, but long parallel runs next to VFD motor feeds or elevator power can wake up ghosts, especially with older device bases or marginal connections. I prefer at least 12 inches of separation from high-voltage runs, more when practical. In retrofit work where sharing a tray is unavoidable, metal dividers help, and twisted pair for the SLC limits inductive pickup. It is not glamorous, but it saves weekends.
Annunciation, mapping, and operator clarity
Wiring topology only helps if the operators can see what’s going on. An annunciator panel setup that mirrors building zones, with clear labels tied to actual device addresses, prevents the deer-in-headlights moment when a device disappears from the loop. I’ve stood next to building engineers during an alarm while they page through binders trying to cross-reference an address with a floor plan. Digital mapping integrated with the fire alarm panel connection makes faults obvious: you see the break between device 143 and 144 on the west riser, Level 9. That changes how fast someone can verify the condition and start repairs.

When cost, schedule, and code collide
For owners balancing budgets, the first question is always: how much more will Class A cost? The answer ranges from modest to significant. Expect more cable, more terminations, more isolators, and more coordination with other trades. On a mid-rise residential building with four risers and 20 floors, a well-routed Class A SLC design might add 10 to 20 percent to SLC material and labor compared to Class B. In healthcare or lab buildings with compartmentalization, the increase can be higher because you’re routing returns along distinct, code-compliant pathways. That said, many service departments will tell you that Class A saves callbacks caused by incidental cable damage during tenant improvements.
Schedule also matters. If ceilings are closing and you have only one riser path approved by the AHJ, forcing Class A into the same conduit is a hollow victory. Engage the AHJ early, explain your life safety wiring design goals, and seek agreement on pathway diversity. Code-compliant fire systems are built with the authority having jurisdiction, not shown to them at the finish line.
Device layout, detector bases, and avoidable pain points
Smoke and heat detector wiring rules of thumb can clash with architectural intent. In hotels with ring corridors, Class A makes sense because you can send the SLC around the ring both directions, placing isolators near stair doors. That way a cut near a guest room only affects a small section. In long, straight corridors of office towers, create virtual rings by using vertical risers at each end of the floor and crossing over once per quadrant rather than in the middle. Field terminations in device bases should be neat, with torque-checked screws and clean insulation strips. Loose strands cause the kind of intermittent opens that seem to appear only during fire marshal inspections.
Addressable bases that include relay contacts or sounder bases add complexity. Keep relay and alarm relay cabling separate from the SLC conductors in the base. I’ve seen field techs loop NAC conductors through SLC terminals or zip-tie them together for convenience. That invites crosstalk and makes troubleshooting miserable. Your alarm panel connection points will record weird device resets and late acknowledgments that look like firmware bugs until you find a base with three different functions smashed together.
Testing that matches topology, not habit
Commissioning should reflect the way the circuit is supposed to survive faults. For Class B, confirm that an open beyond device N takes all downstream devices off the map and that the panel annunciates the trouble correctly. For Class A, break the loop at multiple points, confirm that all devices on both sides remain visible, and check that the panel identifies a single open rather than throwing false short troubles. Introduce a controlled short to verify isolators operate, then measure what portion of the loop loses communication. If half the floor drops, you need more isolators or better placement.
Don’t forget end-to-end voltage and current measurements under load. With long SLC runs, borderline devices expose themselves when you ring the NACs and charge auxiliary door holders simultaneously. Watch for panels that dip their SLC output during heavy NAC activity. If you see spurious device missing troubles during full notification, consider rebalancing power supplies, adding a dedicated SLC power booster if the manufacturer supports it, or revisiting your NAC power distribution.
Integrations that tug on wiring choices
Modern systems are more than detectors and horns. BMS interfaces, smoke control, elevator recall, fireman’s phone, and mass notification change priorities. If your safety communication network relies on distributed amplifiers, backbone survivability is more important than whether every spoke is Class A. If your smoke control sequences depend on control modules scattered through mechanical rooms, give those paths special attention and isolate them from tenant buildout runs that will get touched during remodels.
For elevator recall, elevator machine rooms often sit in electrically noisy environments. Keep the SLC Class A, route the return path through a separate riser where possible, and put an isolator near the machine room door. It compartmentalizes common failure zones and keeps the rest of the floor stable if someone lands a scissor lift on a conduit.
Documentation that aging buildings can live with
Five years after turnover, someone will open your panel and try to make sense of your work. If you documented the SLC device order and the isolator map, the next technician can trace faults quickly. If you didn’t, the building goes into extended trouble while they guess. Provide laminated one-line diagrams at the panel and at major remote power supplies. Mark Class A outbound and return legs distinctly, using color-coded ferrules or sleeves if allowed. Label junction boxes with circuit ID and direction. When you pull two loops through a shared space, print labels every 20 to 30 feet. Ink fades, and remodels happen.
Edge cases: mixed modes and partial Class A
Not every system is pure. You may have a Class A SLC with a few Class B stubs feeding legacy wings. Or a core building SLC in Class A, with tenant floors on Class B until a future upgrade. Mixed-mode design is fine if you understand the implications. The moment a segment goes Class B, a single open isolates everything past that point. Use isolators at the branch to fence in the risk. Make sure the annunciation notes that devices 301 to 350 sit on a Class B spur so the operator knows what to expect during a fault.
Another edge case is loop length. Some panels allow long SLC distances, but voltage and signal integrity still matter. Class A effectively doubles your path length. Check the manufacturer’s total loop length specification for Class A versus Class B, and https://rentry.co/r2h7xqsg measure actual loop resistance after installation. In tall towers, you may need to split floors across two SLC loops to stay within limits. It’s not a defeat, it’s good engineering.
Coordinating with the AHJ and other trades
Early coordination solves most headaches. Show the AHJ how your Class A return paths avoid common conduits and shafts. Confirm they accept your use of isolators to segment faults. Coordinate with electrical to keep your routes away from noisy feeders and to reserve space for future branches. If you need to pass through a rated assembly, confirm you have the correct firestopping detail. Keep your emergency evacuation system wiring isolated from tenant low-voltage bundles that IT installers might tug later. The minute your cable sits in their tray, assume it will get moved.
Practical, field-ready pointers
Here is a short checklist I share with new team members when we plan smoke and heat detector wiring. It embraces the realities of both Class A and Class B while keeping code-compliant fire systems front and center.
- For Class A, route the return leg along a different pathway whenever possible, especially across vertical transitions. Place isolators to bracket high-risk areas: mechanical rooms, electrical rooms, long corridors, and floor-to-floor transitions. Keep EOL resistors at the last device, physically in the field, and verify during punch by opening the box. Separate SLC and NAC conductors in device bases, and keep relay and auxiliary power wiring tidy and distinct. Test faults the way they will occur in real life: opens, shorts, and heavy NAC load while polling the full SLC.
Budgeting with eyes open
Owners deserve plain language. A Class B layout is less expensive and faster to install, with acceptable performance in many occupancies. A Class A layout costs more in wire, labor, and coordination but preserves operation through single faults and typically reduces service downtime. On multi-phase projects, I sometimes phase in Class A by starting with risers and core floors, then converting tenant floors during turnover. This approach spreads cost while improving survivability where it matters most.
Mass notification cabling for voice adds another dimension. A well-designed backbone with distributed amplification and supervised speaker circuits, routed with the same care as a Class A SLC, can outperform any paper-strong but pathway-weak approach. Site conditions, not marketing tags, determine real reliability.
The bottom line for your design decision
Class B provides simplicity, speed, and cost savings. It shines in smaller or lower-risk occupancies where a single open fault can be managed operationally without jeopardizing life safety. Class A provides resilience against single opens and, with isolators, localizes shorts so the rest of the loop stays alive. It demands more planning and discipline in routing. If your building depends on continuous monitoring and coordinated control, or if construction churn makes cable damage likely, Class A is usually worth the investment.
Whichever path you choose, the fundamentals do not change. Route smart, isolate risks, supervise correctly, and test in ways that reflect the real forces that act on a building. Get the alarm panel connection right, keep annunciation truthful and clear, and protect your safety communication network from the casual errors that sabotage good designs. Do that, and your wiring topology becomes the quiet workhorse it’s meant to be rather than the star of your service log.